Parker Products COMPAX-M /-S (L) User Manual

Page of 242
Interfaces
Digital inputs and outputs
151
Unit
hardware
Connector
assignment / cable
Technical data
Configuration
Positioning and
control functions
Optimization
functions
Interfaces
Accessories /
options
Status
Parameter
Error list
Input I15 
Special START input
 
Input for fast and defined starting of positioning process.
 
The "Fast start" function is switched on using P18=2 or 3 (when using P18=3, the
PLC data interface is also switched on).
 
When I15="0", all positioning processes (POSA, POSR) are blocked.
 
When I15="1", positioning processes are started. I15 has no influence during a
positioning process.
 
A positioning process interrupted with STOP is continued using START (I5="1")
and "Fast START" (I15="1").
 
The reaction time of I15 before the start of the positioning process is 1.5 ms.
 
I15 has no effect in speed control mode.
Note!
The START signal (I5) is not replaced by I15; after STOP, a START
signal (I5) is required to start the program and for WAIT START.
8.6.1.6  Synchronous STOP using I13
I13 in the standard model (COMPAX XX00) provides a STOP function with which
you can stop and idle multiple COMPAX units simultaneously, regardless of the
current speed.
P219=128 or 135 enables the synchronous stop via I13 (P219 bit 7
I13="1": Normal mode
I13="0": Synchronous STOP is activated.
After I13="0"
 
the drive is stopped using P10 as the absolute ramp time and
 
 
Error message E08 is output,
 
O1 is set to 0 and
 
the ready contact is opened.
While I13=0, any further positioning attempts are negatively acknowledged with
E08. No negative acknowledgment comes from HEDA.
Synchronous STOP function using I13 is only available on the standard unit
(COMPAX XX00).
Stop using I6
Stop using I13
2...5ms
60%
100%
t
t
P10
STOP
(I6)
The same
brake ramp
Speed
COMPAX 1
Speed
COMPAX 2
<1,1ms
STOP
(I13)
Brake ramp
P10 (absolute)
Speed
COMPAX 1
Speed
COMPAX 2
P10
Using I13 for stop bring both axes to a stop simultaneously.
                      
36
  Bit counting begins with bit 0.
37
  A modified ramp time is used after "VC" for the "Synchronous stop via I13"
function.
Fast start
Synchronous
STOP:
Diagram: