Trane OA1D OA2D OA3D (Indirect Gas-Fired/Electric Heat) Maintenance Manual

Page of 56
Sequence of Operation
22
 OAU-SVX01E-EN
Optional Features
Digital Compressors
Main unit controller will modulate digital compressor to 
maintain either evaporator leaving or space temperature 
setpoints depending on mode of operation. Remaining 
compressors will be staged as described in mode.
ERV and Powered Exhaust
ERV and powered exhaust are interlocked with indoor fan 
operation in occupied heating, dehumidification or 
cooling modes. Outdoor air sensors sending temperature 
and Rh signals to the main unit controller to make mode 
calls are relocated downstream of the ERV. Outdoor air 
heating and dehumidification override setpoints will be 
based on ERV leaving conditions. Additional sensors will 
be installed in the non-ERV outdoor air position for 
information purposes and those outdoor air readings may 
be viewed at the main unit controller or via the BAS. When 
operating in economizer mode the ERV is disabled and the 
ERV by-pass damper(s) open, powered exhaust remains 
on and is adjusted to 100  percent capacity by the main unit 
controller. The main unit controller will end ERV operation 
and open ERV bypass dampers if outdoor air/return air 
conditions could cause ERV frosting, powered exhaust 
remains on.
Note: For units with optional ERV defrost heater, the 
control sequence will engage heater at frost 
condition rather than stop ERV.
The powered exhaust fan speed is factory set to run 
between 50 percent and 100 percent (field adjustable).
Hot Gas Reheat
Following continuous 30-minute hot gas reheat operation 
at less than 100 percent reheat capacity a purge cycle will 
be initiated. During the purge cycle the, hot gas reheat 
signal is set and held at 100 percent for a period of 
3 minutes. Following the purge cycle, normal operation 
resumes.
Sequence of Operation—”Unoccupied”
Emergency Stop. 
When the contacts at Terminal 
OAUTS 9 and 10 are open, the unit’s operation will be in 
Alarm Status. The Alarm must be reset from either the BAS 
or the optional on-board unit display.
Starting Sequence
Indoor fan proving sequence is identical to occupied 
operation.
Starting Sequence with Optional Return Air 
Damper Installed
The outdoor air damper will be commanded to close and 
the return air damper will open. Outdoor air damper end 
switch is disabled when the return air damper is installed.
Starting Sequence with No Return Air Damper 
Installed. 
Identical to occupied sequence no return air 
damper installed. 
Operating Modes
A. Unoccupied Heating
B. Unoccupied Dehumidification
C. Unoccupied Cooling
A. Heating Mode. 
Unoccupied heating is enabled 
based on unoccupied space heating setpoint. Unoccupied 
heating is enabled when space temperature reaches 
unoccupied space heating setpoint - 2°. The modulating 
gas heat or SCR electric heat will continue to raise the 
discharge air temperature to a maximum of 90°F and 
continue to supply heated 90° air to the space until the 
space temperature reaches setpoint +  2°. Unit operation is 
discontinued when unoccupied space heating is satisfied.
B. Dehumidification Mode. 
When no call for 
unoccupied heating exists, unoccupied dehumidification 
is enabled based on unoccupied space dewpoint setpoint. 
During unoccupied dehumidification operation 
dehumidification capacity is restricted to 50 percent (only 
half of the compressors are allowed to come on). 
Unoccupied dehumidification is enabled when space 
temperature reaches unoccupied space dehumidification 
setpoint + 1°. Dehumidification stops at setpoint - 1°. Unit 
operation is discontinued when unoccupied space 
dehumidification is satisfied.
C. Cooling Mode. 
When no call for unoccupied heating 
or unoccupied dehumidification exists, unoccupied 
cooling is enabled based on unoccupied space cooling 
setpoint. During unoccupied space cooling operation 
cooling capacity is restricted to 50  percent (only half of the 
compressors are allowed to come on). Unoccupied 
cooling is enabled when space temperature reaches 
unoccupied space cooling setpoint + 2°. Cooling stops at 
setpoint - 2°. Unit operation is discontinued when 
unoccupied space cooling is satisfied.
Powered Exhaust/ERV Sequence of Operation
Powered Exhaust/ERV operation is disabled during unit 
“Unoccupied” operating modes.