Trane OA1D OA2D OA3D (Indirect Gas-Fired/Electric Heat) Maintenance Manual

Page of 56
Installation
OAU-SVX01E-EN
31 
Controls Using DC Analog Input/Output 
(Standard Low Voltage Multiconductor 
Wire)
Before installing any connecting wiring between the unit 
and components utilizing a DC analog input\output signal, 
refer to 
, an
 for the electrical access locations provided on the 
unit.
1.
 lists the conductor sizing guidelines that 
must be followed when interconnecting the DC binary 
output devices and the system components utilizing a 
DC analog input\output signal to the unit.
Note: Resistance in excess of 2.5 ohms per conductor 
can cause deviations in the accuracy of the 
controls.
2. Ensure that the wiring between controls and the unit’s 
termination point does not exceed 2.5 ohms/
conductor for the length of the run.
3. Do not run the electrical wires transporting DC signals 
in or around conduit housing high voltage wires.
DC Conductors
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote 
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be 
inadvertently energized. Failure to disconnect power 
before servicing could result in death or serious injury.
Table 8.
Zone sensor module wiring
Distance from Unit to Control
Recommended  Wire Size
000–150 feet
0–45.7 m
22 gauge
0.33 mm
2
151–240 feet
46–73.1 m
20 gauge
0.50 mm
2
241–385 feet
73.5–117.3 m
18 gauge
0.75 mm
2
386–610 feet
117.7–185.9 m
16 gauge
1.3 mm
2
611–970 feet
186.2–295.7 m
14 gauge
2.0 mm
2
Figure 31.
OAUTS Connection B