Trane OA1D OA2D OA3D (Indirect Gas-Fired/Electric Heat) Maintenance Manual

Page of 56
52
 OAU-SVX01E-EN
Alarms and Troubleshooting
Microprocessor Control
The Main Unit Display and RTRM have the ability to 
provide the service personnel with some unit diagnostics 
and system status information.
1.
Verify that the Liteport LED on the RTRM is burning 
continuously. If the LED is lit, go to 
2. If the LED is not lit, verify that 24 Vac is presence 
between J1-1 and J1-2. If 24 Vac is present, proceed to 
. If 24 Vac is not present, check the unit main 
power supply, check transformer (TNS1). Proceed to 
 if necessary.
3. Utilizing “Method 1” in the RTRM “System Status 
Checkout Procedure”, check the following:
System status
Cooling status
If a System failure is indicated, proceed to 
failures are indicated, proceed to 
4. If a System failure is indicated, recheck 
 an
. If the LED is not lit in 
, and 24 Vac is present in 
, the RTRM has failed. Replace the RTRM.
5. If no failures are indicated, use one of the override 
options to start the unit. Following the Override 
procedure will allow you to check all of the operating 
modes, and all of the external controls (relays, 
contactors, etc.) for each respective mode.
6. Refer to the sequence of operations for each mode, to 
assist in verifying proper operation. Make the 
necessary repairs and proceed to 
.
7.
If no abnormal operating conditions appear in the 
Override mode, release the override and turn the 
power “Off” at the main power disconnect switch.
System Alarms
The Main Unit Display has built in alarms to help the 
operator troubleshoot system failures. This section will 
describe these alarms and provide a guide to 
troubleshooting the all unit operating modes.
Comprehensive system alarms and diagnostics are 
accessed through the Alarms icon at the unit display 
discussed later in the section, or through Tracer TU 
programming on connected computer. Sensor failures 
may be viewed through the Alarms icon.
If an alarm is present, the main indicator light on the 
UC600 will blink red. If the optional unit display is installed, 
the Alarm icon on the display will register ALARM, 
illuminate red and flash.
Important:
The space temperature sensor (SPTC) and 
space relative humidity sensor (SPHC) will 
read failed if they are not connected; they 
will Alarm as “In Fault.”
Sensor Failure Alarm Display
Press the Alarm button on the Home display of the Unit 
Display to display system sensor status as described in 
.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures 
recommended in this section of the manual could result 
in exposure to electrical, mechanical or other potential 
safety hazards. Always refer to the safety warnings 
provided throughout this manual concerning these 
procedures. When possible, disconnect all electrical 
power including remote disconnects before servicing. 
Follow proper lockout/tagout procedures to ensure the 
power can not be inadvertently energized. When 
necessary to work with live electrical components, have 
a qualified licensed electrician or other individual who 
has been trained in handling live electrical components 
perform these tasks. Failure to follow all of the safety 
warnings provided could result in death or serious 
injury.
Table 17.
TOAU UC600 alarms 
Point Diagnostic
Possible Cause
1
Indoor Fan  
Failure
VFD not operating
Outdoor and/or Return Air Dampers not 
Operating Properly
Indoor Fan Motor Failure
Indoor Fan Failure Switch IFFS (pressure) 
Failure
IFFS Tubing damaged or not properly 
connected
Refer to startup procedure
3
OAD Proving 
Switch
No voltage at actuator
Failed OAD power transformer
No continuity thru end switch (check at UC)
Note: If unit optional RA damper is 
installed, send switch on OAD is always 
proven
6
Discharge Air 
Temp Source 
Failure
BAS communication down
Failed sensor or improper sensor 
installation
8
Fire Shutdown
BAS ONLY
10
Low Temp 
Lockout
Heat Overridden OFF
Compressor(s) Overridden ON
Setpoint Failures Incorrect
DAT sensor malfunction
Reference 
 for heat failure 
issues