JKSSS+ Series - 67
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.12 System Setpoints (Setpoint Page 12)
(Security Level: 3)
MENU
PAGE 12    SYSTEM
SETPOINTS
DEFAULT DISPLAY 
SCREEN
(Hit DOWN ARROW eleven times)
METERING DATA
PAGE #: 1
Enter Metering Page (1 - 4)
Number for display
METERING DATA
SCREEN #: 1
ALARMS
THERMAL REGISTER
SETUP INFORMATION
PRESS ENTER TO CLR
THERMAL REGISTER
RTD FAILURE ALARM
ALARM:  DISABLED
THERMAL REGISTER 
ALARM:  90%
HOT STALL TIME
:  1/2 O/L CLASS
STOPPED COOL DOWN
TIME:  30  MIN
RUNNING COOL DOWN
TIME:  15  MIN
COLD STALL TIME
:  O/L CLASS
RELAY MEASURED COOL
RATES:  DISABLED
Enabled or Disabled
Range: Off, 40 - 95%
Increments of 1
Range: O/L CLASS, 
             4 - 40 SEC
Increments of 1
Range: 1/2 O/L CLASS, 
             4 - 40 SEC
Increments of 1
Range: 10 - 300 MIN
Increments of 1
Range: 10 - 300 MIN
Increments of 1
Range:  ENABLED or 
              DISABLED
THERMAL ALARM
DELAY:  10 SEC.
Range: 1 - 20 SEC.
Increments of 1
Enter Metering
Screen Number for display
MOTOR DESIGN AMBIENT
TEMPERATURE:  40 C
MOTOR DESIGN RUN
TEMPERATURE:  80% MAX
MOTOR STATOR MAX
TEMPERATURE: INS CLS
THERMAL REGISTER
MINIMUM: 15%
I/B INPUT TO THERMAL
REGISTER:  ENABLED
Range: 10 - 50%, OFF
Increments of 1
Range: 10 - 90 C
Increments of 1
Range: 50 - 100% of Motor 
            Stator Max Temp.
Increments of 1%
Range: Insulation Class
            10 - 240 C
Increments of 1
Options:  ENABLED or 
                 DISABLED
USE CALCULATED K OR
ASSIGN:  7
Range:  1 - 50, ON