Toshiba 18 - 1250 A User Manual

Page of 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
12 
3.1.3   Disabling the Overload Protection 
The Overload Protection feature can be disabled if necessary. When 
using external devices such as Motor Protection Relays or when the TE 
Series
 is wired downstream from an existing starter, this feature can be 
disabled to prevent conflicts with external overload protection devices. 
When the TE Series is controlling multiple motors, the built-in Overload 
protection must be disabled and individual thermal overload relays must 
be installed on the motor leads going to each motor (see appendix 5 for 
additional details). To disable the Overload Protection function, use 
F005.  
 
    WARNING
  
Do NOT disable Overload Protection unless another Thermal Overload Protection 
device exists in the circuit for all three phases. 
Running a motor without Overload 
Protection presents serious risk of motor damage or fire. 
 
ƒ  3.1.3.a  
Manual Reset 
The factory default setting is Manual Reset. This means that when 
the Overload Trip is activated, the starter cannot be restarted 
without pressing the Reset key. The Overload Trip will not reset 
until the motor cools down (see 3.1.3.d). The Manual Reset function 
is also “trip free”. Holding in the Reset key will not prevent the 
Overload Trip from activating and protecting the motor. 
 
ƒ  NOTE:  
When the Overload Trip activates, the Overload LED will glow solid. 
When the motor cools down, the LED will begin to flash, indicating 
that the Overload Trip can be reset. 
 
ƒ  3.1.3.b  
Automatic Reset 
If Automatic Reset is necessary, change from Manual Reset to 
Automatic Reset by using Function F005. (See Section 5 for 
details). In this mode, a 3-wire control circuit will be capable of 
restart when the TE Series has reset itself after the cool down 
period. 
 
    WARNING
  
Two-wire control systems may restart without warning when Auto 
Reset of the overload protection is selected. Extreme caution 
should be exercised. To prevent automatic restarting with 2-wire 
control systems, use external interlocking to provide sufficient 
warning and safety to operators. A Warning Label similar to that 
shown below (and the one provided in the packet with this manual) 
must be located where visible (on the starter enclosure and/or the 
driven equipment) as required by local code. 
 
 
 
 
WARNING: MOTOR CONNECTED TO THIS EQUIPMENT
MAY START AUTOMATICALLY WITHOUT WARNING