14
 
 Continuous operation depends on the status information that was before the communication error happens.
z
 
Display of communication error will be [t].
z
 
Display of trip will be [err8].
z
 
When interrupting a transmission to change the setting of command input, reboot a power supply if
necessary, since the data which have been received before the interruption of transmission are stored in
the inverter.
z
 
Parameter setting of smaller communication number will be valid in case that the same setting values are
allocated to the command input setting which are between 1 and 6, and also to the monitor output setting
between 1 and 6.
 (Note 3) The setting of communication error detection time is relating to the number of stations connected
 to the communication line. When changing the setting, fully consider the number of connected stations.
 
„
  Other parameters
 The following parameters reflect the transmitted data in the control of the inverter.
Parameter name
Title
Setting value
Details
Operation
command mode
selection
cmod
4
 Validates the command sent from the F10M option.
Operation such as run/stop from the other station will be
possible.
Speed setting
mode selection
fmod
9
Validates the speed reference value from the F10M option.
Torque command
selection
f420
9
Validates the torque command value from the F10M option.
Selection of
synchronized
torque bias input
f422
5
Validates the synchronized torque bias from the F10M
option.
Selection of
tension torque
bias input
f423
5
Validates the tension torque bias from the F10M option.
Load sharing gain
input selection
f424
5
Validates the load sharing gain from the F10M option.
Power running
torque limit 1
selection
f440
5
Validates power running torque limit from the F10M option.
Selection of
regenerative
torque limit 1
f442
5
Validates regenerative torque limit from the F10M option.