Omron ZS-MDC User Manual

Page of 94
3-16
Section 3
SETUP
ZS-MDC
User’s Manual
Section 3
Setting I/O Assignments
Setting I/O Assignments
Switching banks by external signal input
Set the task or function to the external input. 
If you use SmartMonitor Zero, you can change the function assignments of IN2 and IN3 if [BANK] is
selected. For details, refer to the Help for SmartMonitor Zero.
FUN mode-[I/O SET]-[I/O SET]-[IN]
For bank inputs A and B, the bank can be selected in the following combinations.
• Bank switching is begun 0.5 seconds after the input state changes.
• At most it takes about 10 seconds to switch banks.
• During bank switching the BUSY output becomes ON.
Setting
Description
TASK
Select to task for enabling the external signal lead. Note, however, that reset input 
and bank inputs affects tasks at all times. 
Range: TASK1 to TASK4, TASK-ALL
FUNC
NORMAL
Select this to use external input function as in standard applications so far (default 
value).
IN0
IN1
IN2
IN3
External trigger 
(timing) input
Reset input
Unused
Zero reset input
BANK
Select this to switch banks using external inputs.
IN0
IN1
IN2
IN3
Bank input A
Bank input B
Unused
Zero reset input
Bank to be Selected
Bank input A
Bank input B
BANK1
OFF
OFF
BANK2
OFF
ON
BANK3
ON
OFF
BANK4
ON
ON