10b.1: First Level: Press SET + UP for 6 Seconds 
t10    Compressor start time delay; 1 to 30 min adjustable. Factory setting 10 min. 
p10    Interval for compressor start after stop; 3 to 30 min adjustable. Factory setting 10 min. 
d10    Interval for over heat auto-reset; 3 to 30 min adjustable. Factory setting 10 min. 
E10    The max de-icing time; 5 to 30 min adjustable. Factory setting 10 min. 
F45    The interval for de-icing; 10 to 99 min adjustable. Factory setting 45 min. 
10b.2: Second Level: Press SET+DOWN for 6 Seconds 
A65    Highest water temperature setting; 30 to 65℃  adjustable. Factory setting 65℃. 
d05    Temperature difference for heat pump reactivation (H55 - d05=50℃) 5 to 30℃ adjustable. 
Factory setting 5℃. 
H95    Overheat trip-out temperature; 60 to 98℃  adjustable. Factory setting 95℃. 
L70  Overheat reset temperature; 60 to 98 adjustable. Factory setting 70℃. 
P85    Liquid Injection activation temperature; 55 to 98℃  adjustable. Factory setting 85℃. 
b75    Liquid Injection de activation temperature; 55 to 98℃  adjustable. Factory setting 75℃. 
F08    De-ice de activation temperature; 1 to 15℃  adjustable. Factory setting 8℃. 
C-5    De-icing temperature setting; -9℃ to -1℃; Factory setting -5℃. 
10b.3: Third Level: Press UP+DOWN for 6 Seconds 
FXX    Start Up model; F00 to F03 adjustable. Factory setting F02. 
F00    Following compressor start the Liquid Injection & De Icing valves remain closed. 
F01    Following compressor start the Liquid Injection valve opens, 3 seconds later it closes. 
F02    Following compressor start the De-Icing valve opens, 3 seconds later it closes. 
F03    Following compressor start the Liquid Injection & De Icing valves open, 3 seconds later they 
close. 
A25    Compressor amperage overload adjustment; 0 to 30 Amps adjustable. Factory setting 25A. 
10c: Error Codes 
E01    Water temperature sensor open or short circuit. Auto reset. 
E02  Compressor temperature sensor open or short circuit. Auto reset. 
E03  Evaporator temperature sensor open or short circuit. Auto reset. 
E04    Compressor overload protection. Auto reset the first time, manual reset the second time. 
E05    Compressor overheat protection (exceeding H95 setting). Auto reset. 
E06    Compressor overheat protection (exceeding 105℃). Manual reset. 
E08    Ambient temperature sensor open or short circuit (Optional). Auto reset.