Operational Change in SmartModule Systems 
When a CAT-3 SmartController is used in an Adept SmartModules system, or an Adept 
Servo Kit system, that includes a PDU-2, there is a minor change in operation compared to 
the original SmartController. The sequence would be:
1. In a SmartModule system with a CAT-3 SmartController, while operating in 
Manual Mode, power is turned off by releasing the Enable switch on the MCP.
2. To re-enable power, the user must press and hold the Enable switch.
3. Next the user must press the Cmp/Pwr button on the MCP.
4. Then the user must press the High Power button on the Front Panel to turn on 
High Power to the robot. The LCD display on the MCP will instruct the user to 
press the button. The button will be blinking, and must be pressed within 10 
seconds. (Ten seconds is the default timeout for the High Power button to be 
pressed. This timeout can be changed using the CONFIG_C utility.)