Nortech Systems Adept RS-232/TERM User Manual

Page of 156
Connecting Customer-Supplied Safety and Power Control Equipment
Adept SmartController User’s Guide, Rev. E
49
3.7
Connecting Customer-Supplied Safety and Power Control 
Equipment
Connecting Equipment to the System
The connection of the customer-supplied safety and power control equipment to the 
system is done through the XUSR and XFP connectors on the SmartController. The XUSR 
connector (25-pin) and XFP (15-pin) connector are both female D-sub connectors located 
on the front panel of the SmartController. Refer to 
 for the XUSR pin-out 
explanations. Refer to 
 for the XFP pin-out explanations. See 
 for the XUSR wiring diagram.
Table 3-7. Contacts Provided by the XUSR Connector
Pin 
Pairs
Description
Comments
Shorted if 
NOT Used
Voltage-Free Contacts Provided by Customer 
1, 14
User E-Stop CH 1 (mushroom PB, 
safety gates, etc.).
N/C contacts
Yes
2,15
User E-Stop CH 2 (same as pins 1 
and 14).
N/C contacts
Yes
3,16
Line E-Stop (used for other robot or 
assembly line E-Stop 
interconnection. Does not affect 
E-Stop indication (pins 7, 20.))
N/C contacts
Yes
4,17
Line E-Stop (Same as pins 3 and 16. 
See above comment.)
N/C contacts 
Yes
5,18
Muted safety gate CH 1 (causes 
E-stop in AUTOMATIC mode only). 
N/C contacts
Yes
6,19 
Muted Safety Gate CH 2 (same as 
pins 5 and 18).
N/C contacts
Yes
Voltage-Free Contacts provided by Adept
7,20
E-Stop indication CH 1.
Contacts are closed when 
Front Panel, MCP, and 
customer E-Stops are not 
tripped
8,21
E-stop indication CH 2 (same as pins 
7 and 20.
Contacts are closed when 
Front Panel, MCP, and 
customer E-stops are not 
tripped
9,22
MANUAL/AUTO indication CH 1
Contacts are closed in 
AUTOMATIC mode