Kuma Stoves OC-10 User Manual

Page of 11
The air duct does not need to connect directly to the stove as the duct may terminate at the 
hearth top level.  If air is accessed through the wall, remove the air cover at the stove pedestal 
back, and install a 4” or larger duct connecting the stove pedestal and the wall.  A storm or 
dryer type vent with a screen is adequate.  For your convenience, an outside air kit (part # 
4OAVK) is available through your dealer.  All mobile home installations require use of 
OCHM1 Manufactured Home Kit which includes an automatic oil valve shut-off control rod, 
return spring, and all fasteners.  Complete mobile home kit installation instructions are included 
with this kit.  For further help or questions, contact your dealer. 
 
If you are not installing this stove in a mobile home, and outside air is not desired, 
simply remove the outside air cover at the pedestal back so ambient room air can enter.  Please 
note that at certain draft conditions (i.e. high winds) a significant amount of air may be needed 
to achieve a proper burn.  Consideration of open windows or an air source near the stove will 
probably be necessary depending on the “air-tightness” of your home.  Again, outside air to 
your oil stove is a good idea as it will make the combustion impervious to house pressure 
problems. 
 
 
*Please note that these clearances are minimums.  It is a good idea to exceed these  
             clearances unless space is limited.  Common sense must prevail. 
 
Minimum Clearances to Combustibles 
 
 
 
 
Sides   
Back          Flue Pipe 
    Corner 
     Top 
 
Standard 
 
  8”   
  6”   
   9”*  
        4” 
      — 
 
Alcove 
 
  8”   
  6”   
   9”   
        4” 
      54” 
 
 
 
 
Note:  Corner clearance applies only when the stove is installed in a room 
 
 
 
corner with the stove placed perpendicular to the corner (45 degrees). 
 
 
 
Note:  On alcove installations, the maximum depth of the alcove is 30”. 
 
 
 
 
*Clearances to flue pipe are for single-wall connectors.  A double-wall  
 
 
 
   connector is required for mobile home installations. 
 
SECTION 2 
The flue and flue connections
 
 
 
Do not connect this unit to a flue servicing another appliance.  It is of utmost importance 
that the flue be dedicated to the Oil Classic as the flue is, without a doubt, the most important 
component of the system.  Good combustion is dependent upon the correct amount of air being 
supplied to the burner at all times, which is dependent upon a correct negative flue pressure. 
Draft is caused by the gases inside the flue being hotter and lighter than the air outside, thus the 
rising heated gases carry out the products of combustion.  Since the flue “sucks” gases up the 
flue, it is this suction that draws air into the pedestal area to feed the burn pot with the air 
needed for an efficient, blue-flame burn.     (continued…)