Kidde Fire Systems VEGA LT TM0081 User Manual

Page of 51
TM0081      
Page 51 of 51
 Issue 1.01
17.
TECHNICAL SPECIFICATION
Model number
LT 2000
LT 2001
Protocol
Apollo
Hochiki
Number of detection loops
1
1
Loop circuit load (maximum)
250mA
250mA
Devices  supported
S90, XP95, Discovery, Explorer
ESP
Number of  zone LED indications
16
Number of status LED indications
8
Number of Sounder circuits
2 - programmable
Sounder circuit (shared load)
1 A at 24V dc nominal
End of line unit
10 K ohms resistor
Number of auxiliary relays
2 x NC,C,NO volt free contacts - programmable
Auxiliary relay contact rating
1A at 24V dc
Design standard
EN54 part 2 & 4
Panel dimensions (mm)
460mm (W) x 342mm (H) x 148mm (D)
Weight (no batteries)
8Kg
Knock outs
14 Top
Colour and finish
Ash grey semi-gloss light textured
IP rating
30 (indoor use)
Operating temperature & humidity
-5ºC to 40ºC. Max relative 93%
Emission
BS EN50081-1:1992:part 1 Residential, Commercial and Light industry
Class B limits
Immunity
BS EN50130-4: 1995: part 4 alarm systems: Electromagnetic compatibility
Product family standard: immunity requirements for components of fire,
intruder and social alarm systems
Power supply rating
2.5Amp at 24V dc
Mains operating voltage
110V to 230V ac – 50Hz to 60Hz
Battery supply (integral)
2 x 12V 12Ah
Battery standby with 40mA loop
load & 0.5A sounder alarm load
24Hr standby plus 0.5Hr during alarm
Buzzer for local audible indication
Fire & System fault – continuous sound.  Fault – intermittent sound using
piezoelectric buzzer operating at 60 dB (A) at 1 m
Common fault relay contact
Normally On – 1 x NC and 1 x NO contacts
External fault input
Internal switched 0V input
Access level 2 input
Internal switched 0V input - allows keyswitch enable
Programmable MBLC input 7
Internal switched 0V inputs – Remote evacuate (default setting) or day
mode control or Isolate output groups
Programmable MBLC input 8
Internal switched 0V input – Day mode control (default setting) or Isolate
output groups or Remote evacuate
Number of repeater panels
supported
A maximum of 10 repeater panels - 6 with optional user controls
Repeater output driver card
Part Number - 44782-K076
Repeater cable specification
Screened  twisted pair - Belden 9841 or similar
Repeater part number
VR3000 or VR3000P
Network support
CZN System or VegaNET Display System
Network card part numbers
CZN - VN2108 & VegaNET – VN2107
Network cable specification
2 x Individually screened twisted pairs – Belden 9729 or similar
Printer type (optional)
Thermal – Part Number VR0053
Detection loop specification
Pirelli FP200 Gold™, MICC (Pyro™), Firetuff™ and Firecel™.
Detection loop length
Cable length up to 1 km use 1.5 mm cross sectional area.
Cable length up to 2 km use 2.5 mm cross sectional area.
Control buttons
Silence buzzer, Scroll alarms, Silence alarms, Reset, Delay override,
Evacuate, Numeric keypad and User cursors
Visual indications
Alarm, Fire Output  & Zones – Red LEDs ‘lights’
System fault, Disablement, Fault, Test, Fire output – Yellow LEDs ‘lights’
Power On – Green LED ‘light’
User access via numeric keypad
code entry (default passwords)
Level 1 – No password required
Level 2 – 7179
Level 3 – 7134
Table 22: Technical Specification