Mitsubishi Electronics J2-JRSERIES MR-J2-03A5 User Manual

Page of 185
13 -  8
13. COMMUNICATION FUNCTIONS
13.7 Time-Out Operation
The master station transmits EOT when the slave station does not start reply operation (STX is not
received) 300[ms] after the master station has ended communication operation. 100[ms] after that, the
master station retransmits the message. Time-out occurs if the slave station does not answer after the
master station has performed the above operation three times. (Communication error)
E
O
T
300ms
100ms
E
O
T
300ms
100ms
E
O
T
300ms
100ms
300ms
Me
ss
a
g
e
Me
ss
a
g
e
Me
ss
a
g
e
Me
ss
a
g
e
*Time-out
Controller
(Master station)
Servo
(Slave station)
13.8 Retry Operation
When a fault occurs in communication between the master and slave stations, the error code in the
response data from the slave station is a negative response code ([B] to [F], [b] to [f]). In this case, the
master station retransmits the message which was sent at the occurrence of the fault (Retry operation). A
communication error occurs if the above operation is repeated and results in the error three or more
consecutive times.
Me
ss
a
g
e
Me
ss
a
g
e
Me
ss
a
g
e
*Communication error
Controller
(Master station)
Servo
(Slave station)
S
T
X
S
T
X
S
T
X
S
ta
tio
n num
ber
S
ta
tio
n num
ber
S
ta
tio
n num
ber
Similarly, when the master station detects a fault (e.g. checksum, parity) in the response data from the
slave station, the master station retransmits the message which was sent at the occurrence of the fault. A
communication error occurs if the retry operation is performed three times.