Installation
The following sections describe UPS storage requirements and the installation and
startup of the UPS.
 "      $"%! 
Carefully unpack the UPS and battery modules, making sure to retain the packaging
materials. Examine each unit carefully for any signs of damage and immediately
notify your service representative if damage is present.
   %%#'  !& %!#
If you plan to store the UPS or battery modules prior to use, store them in a cool,
dry environment. Storage temperature should not exceed 35_C (95_F) in order to
preserve battery life. For longer term storage, energize the UPS and battery module
for approximately 8 hours every 90 days in order to maintain battery charge.
Whenever the units are not energized, make sure the circuit breaker on all battery
modules is returned to the OFF (O) position (see Figure 5 on page 26).
"!#% %   $%%!  !%$   !#  $%  % 
UPS applications requiring a serial interface or standard LAN interface may connect
directly to the 25Ćpin UPS alarm interface. PBXsystems such as the DEFINITYr
Communications System and processorĆbased applications such as Call Center,
Conversant, or Voice Processing that use a Remote Management Board require an
isolated contactĆclosure interface that is provided by a special UPS Alarm Interface
Adapter (PEC 24433).
 
       %     !     ! "! 
   $         # !      
      %  !      #    # 
!          # "  "    !  % 
 
         ! !  !        
& !            !      # !
                 !     
   !