Lucent Technologies Uninterruptible Power Systems 3000 VA User Manual

Page of 75
     
Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

         
Input Voltage Range
160 to 276 Vac
Bypass Isolation Module
Input Voltage Range
187 to 276 Vac
Input Power Factor
0.95 Typical
Frequency Range
50/60 Hz 3 Hz
Surge Protection
IEC 801Ć4
Output Wave Form
Sine wave
Output Voltage (without
Bypass Module)
200/208/220/230/240 Vac 3%
Common Mode Noise
Rejection
>60 dB @ 100 kHz
Transverse Mode Noise
Rejection
>80 dB @ 100 kHz
Input Cord
Detachable 2Ćmeter cord with L6Ć30P
Outlets (UPS Module)
IEC 320 (1)
Output Voltages and Outlets
(with BDM)
120/208V: L6Ć30R or L14Ć30R, 4x5Ć15R
120/240V: L6Ć30R or L14Ć30R, 4x5Ć15R
120: L5Ć30R, 4x5Ć15R
208V Hardwired: 120/208V
240V Hardwired: 120/240V
Output Voltages and Outlets
(with BIM)
(208V available with Model 2500 only)
220/230/240V: 1 x IEC 320ĆC19
3 x IEC 320ĆC13
220/230/240V Hardwired: 220/230/240V
Batteries (10) per Module
12 Vdc, 5 Ah, maintenanceĆfree rechargeable lead acid
Battery Module
120 Vdc
Operating Environment
Temperature:10
°
C to 40
°
C
(50
°
F to 104
°
F)
Humidity:
5 to 95%
(noncondensing)
Agency Approvals
Safety:
EN50091Ć1
UL 1778
cUL
EMC:
FCC Part 15 Class A
EN50091Ć2