Liebert 8 Tons User Manual

Page of 72
Site Preparation and Installation
25
Figure 16 Footprint dimensions - outdoor condensing unit
Model
Dimensional Data in. (mm)
Net Weight
lbs (kg) 
60 Hz
50 Hz
Width (A)
Height (B)
Depth (C)
PFC096A-_L
PFH096A-_H
PFC095A-_L
PFH095A-_L
53 (1343)
53 (1343)
36-1/4 (918)
36-1/4 (918)
38-1/2 (978)
38-1/2 (978)
488 (222)
488 (222)
C
A
2 "
B
LEFT
AIR
INTAKE
(51mm)
D
GUARD
HEIGHT
TOP
AIR
DISCHARGE
RIGHT
AIR
INTAKE
SHADED AREA
INDICATES A RECOMMENDED
CLEARANCE OF 18" (457mm)
FOR PROPER AIR FLOW
SHADED AREA
INDICATES A RECOMMENDED
CLEARANCE OF 24" (610mm)
FOR COMPONENT
ACCESS AND REMOVAL
SHADED AREA
INDICATES A RECOMMENDED
CLEARANCE OF 18" (457mm)
FOR PROPER AIR FLOW
REMOVABLE FRONT PANEL FOR
ACCESS TO HIGH VOLTAGE &
LOW VOLTAGE CONNECTIONS
AND REFRIGERATION COMPONENTS
36 1/8 "
4 23/32 "
25 3/32 "
46 7/32 "
53 3/16 "
4 "  TYP.
32 1/8 "
2 "  TYP.
2 "
2 "
(918mm)
(102mm)
(51mm)
(1351mm)
(120mm)
(637mm)
(1174mm)
(51mm)
(51mm)
(816mm)
FOOTPRINT DIMENSIONS
1/2" Bolt-Down Holes
         (6 places)
DPN000131_Rev0