Liebert RCM8CE User Manual

Page of 46
Chapter 3: Main Menu and SubMenus 
 
Liebert RCM8 
 23 
Set Modem Phone Number 2 (3) 
Enter a phone number for another receiving modem (if 
applicable). Press Enter to return to the Modem Setup menu. 
Modem Phone Number 2 is not 
a leased-line option. 
Using an Alpha-Numeric Pager 
When using an alpha-numeric pager, you must enter the 
letter "A" before the pager access code phone number.  
Refer to the sample screen on page 17 of this manual.  
Note: most alpha-numeric paging services do not yet  
support 2400 baud modem connections: use 1200 baud. 
Using a Numeric Pager 
When using a numeric page, an example of the pager 
number that you enter is:  
  
Phone Number 1 = 9,5551212,,,,,911## 
Each comma forces the mode to pause for two seconds.  
The 911 is the user-arranged “code” that identifies the 
page as being from the RCM8. The ## signify the end of 
the pager number and alarm code. 
(See Appendix A on Page A-1 for additional 
modem/pager characters.)  
 
When using numeric pagers, you will have to experiment 
with the number of commas that you need to enter in 
order to get the correct delay before the message is sent. 
 
The Set Pager ID field is left blank when using numeric 
pagers.
 
Set Modem Baud Rate (4) 
Enter 1 for 1200 or 2 for 2400. Press Enter to return to the 
Modem Setup menu. 
Set Dial Prefix (5) 
Press 5 if you need to change the dial prefix. From the 
factory, the Dial Prefix is entered as ATE1X4DT. Do not 
change this dial prefix unless you are thoroughly familiar 
with the Hayes command set. Press Esc to return to the 
Modem Setup menu. 
Set Redial Tries (6) 
Enter a number (0-99) representing the number of times the 
RCM8 will attempt to redial a phone number should the first 
attempt fail. Press Enter to return to the Modem Setup 
menu.