APC Fluid Cooler 57MBH@25 TD, 10GPM, 5Feeds, 400/3/50 ACFC75256 User Manual

Product codes
ACFC75256
Page of 56
5
InRow RD Technical Data Manual
Optional Features
Cable Water Detector
A leak detection cable is placed on 
the floor or subfloor around all possi-
ble leak sources. If water or other 
conductive liquids contact the cable 
anywhere along its length, the micro-
processor controller announces the 
leak visually, audibly, and across the 
network. The 6.1-m (20-ft) cable 
may be cascaded to make custom 
lengths up to 24.4 m (80 ft).
Network Cable
Various lengths of network cable are 
available to ship with your cooling 
system. The network cable is used to 
interconnect multiple cooling units in 
a redundant group, as well as to con-
nect the Network Management Card 
to your LAN.
Filters
Electrical equipment requires clean, 
particle free air, thus making air fil-
tration extremely important. As an 
optional feature, higher efficiency fil-
ters can be purchased for the InRow 
RD units. The ACRD100 and 
ACRD200 series units optionally uti-
lize an 50.8mm (2in) pleated, deep 
loading, 30% ASHRAE 52.1 filter 
(MERV 8 per ASHRAE 52.2). The 
ACRD500 series units optionally uti-
lize 102mm (4in) pleated, deep 
loading, 85% ASHRAE  52.1 filter 
(MERV13 per ASHRAE 52.2). 
Power Trough
Overhead power distribution between 
adjacent NetShelter racks allows for 
removal of the InRow RD without 
disrupting overhead power cabling.
Data Partition
Overhead cable distribution between 
adjacent NetShelter racks allows for 
removal of the InRow RD without 
disrupting overhead cabling.
Height Adapters
To match the height of the InRow RD 
to various rack heights, height adapt-
ers are available for NetShelter 42-U 
VX and 48-U SX racks.