20
Net Cooling Capacity (Water Cooled)
Return Air Temperature
SKU
Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)
22.2°C DB, 15.5°C WB (72°F DB, 60°F WB)
ACRD200
9.72 (33,200)
8.94 (30,500)
ACRD201
9.57 (32,700)
8.79 (30,100)
23.9°C DB, 16.2°C WB (75°F DB, 61.1°F WB)
ACRD200
8.43 (32,200)
8.43 (32,200)
ACRD201
9.30 (31,800)
9.30 (31,800)
26.7°C DB, 19.4°C WB (80°F DB, 67.0°F WB)
ACRD200
11.52 (39,300)
9.90 (33,800)
ACRD201
11.64 (39,800)
9.99 (34,200)
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
ACRD200
10.38 (35,400)
10.38 (35,400)
ACRD201
10.11 (34,500)
10.11 (34,500)
29.4°C DB, 18.1°C WB (85°F DB, 64.6°F WB)
ACRD200
10.92 (37,300)
10.92 (37,300)
ACRD201
10.98 (37,500)
10.98 (37,500)
32.2°C DB, 19.0°C WB (90°F DB, 66.2°F WB)
1
ACRD200
11.64 (39,700)
11.64 (39,700)
ACRD201
11.76 (40,200)
11.76 (40,200)
35.0°C DB, 19.9°C WB (95°F DB, 67.8°F WB)
2
ACRD200
12.00 (41,000)
12.00 (40,900)
ACRD201
12.00 (41,000)
12.00 (41,000)
37.8°C DB, 20.7°C WB (100°F DB, 69.3°F WB)
3
ACRD200
12.06 (41,200)
12.06 (41,200)
ACRD201
12.00 (41,000)
12.00 (41,000)
40.6°C DB, 21.6°C WB) (105°F DB, 70.8°F WB
4
ACRD200
12.06 (41,000)
12.00 (41,000)
ACRD201
12.00 (41,000)
12.00 (41,000)
43.3°C DB, 22.2°C WB) (110°F DB, 72.0°F WB
5
ACRD200
12.06 (41,200)
12.06 (41,200)
ACRD201
12.06 (41,200)
12.06 (41,200)
Airflow for the ACRD200 series is 1081 l/s (2290 SCFM) at full evaporating fan speed.
1
Airflow is reduced to 887 l/s (1880 SCFM) at this condition to maintain adequate evaporating temperature.
2
Airflow is reduced to 717 l/s (1520 SCFM) at this condition to maintain adequate evaporating temperature.
3
Airflow is reduced to 599 l/s (1270 SCFM) at this condition to maintain adequate evaporating temperature.
4
Airflow is reduced to 510 l/s (1080 SCFM) at this condition to maintain adequate evaporating temperature.
5
Airflow is reduced to 448 l/s (950 SCFM) at this condition to maintain adequate evaporating temperature.
Note: Minimum recommended loads: ACRD200 series - 2kW (6,831 BTU)
Note: For ACRD200 series, a 0.64 l/s (10gpm) entering water temperature is 29.4° C (85° F)