InRow RD Technical Data Manual
Guide Specifications
PART 1 — GENERAL
1.01
SUMMARY
A. The environmental control system shall be designed specifically for precision temperature control 
applications. It will automatically monitor and control cooling and filtering functions for the 
conditioned space. The system shall be built to the highest quality engineering and manufacturing 
standards, and shall be floor mounted and configured for horizontal airflow, with draw-through air 
pattern, to provide uniform air distribution over the entire face of the coil.
1.02
DESIGN REQUIREMENTS
A. The system shall be as described in the following specification as manufactured by APC.
1 . Model: ____________________________.
2 . Total net cooling capacity: _______________ kW (MBH).
3 . Sensible net cooling capacity: ____________ kW (MBH).
4 . Return air dry bulb temperature: _______________ ºC (ºF) DB.
5 . Return air wet bulb temperature: _______________ ºC (ºF) WB.
6 . Humidity: __________________________% RH.
7 . Air volume: _______________________ L/s (CFM).
8 . Electrical supply: ____________ V, _________ Hz.
1.03
SUBMITTALS
A. Submittals shall be provided with the proposal and shall include: capacity data, electrical data, 
physical data, electrical connection drawing, and piping connection drawing.
1.04
QUALITY ASSURANCE
A. The system shall be completely factory-tested prior to shipment. Testing shall include, but not be 
limited to: complete pressure and leak testing to ensure system integrity, dielectric withstand test, 
and controls calibration and settings. Each system shall ship with a completed test report to verify 
completion of factory testing procedure. The system shall be NRTL listed, MCA, and the electrical 
system shall be UL Listed to UL 1995 and CSA 22.2 No. 236.
1.05
WARRANTY
A. System parts shall be warranted for a period of 18 months from date of shipment and 12 months 
from startup.
PART 2 — PRODUCT
2.01
STANDARD COMPONENTS
A. Cabinet Construction
1 . Front and rear exterior panels shall be 18 gauge perforated steel with 69.5% open free area, 
and equipped with a keyed lock to provide a means of securing access to the internal 
components of the unit. 
a. ACRD100 and ACRD200 series only: Exterior panels shall be 18 gauge steel with 
80 kg/m
(5 lb/ft
3
) density foam insulation. Insulation complies with UL94-5VA ASTM 
E84 flame spread and smoke developed rating of 25/50.
2 . The frame shall be constructed of 16 gauge formed steel welded for maximum strength. All 
units shall provide maintenance from the front and rear, allowing units to be placed within a 
row of racks.