HP Performance Optimized Data Center (POD) 240a User Manual
Component identification 13
Electrical power component identification
WARNING:
To avoid the risk of personal injury or loss of life, all personnel must comply with PPE
requirements when opening or working inside areas of the HP POD 240e NA that are marked as
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ).
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ).
WARNING:
To avoid the risk of personal injury or loss of life, all personnel must comply with
electrical warning labels when operating and maintaining the electrical panels and systems of the
HP POD 240e NA.
End view shown
Item
Component
Description
1
Demarcation box
Customer communication connection point:
•
ECS
•
Access control
•
Phone
2
Fire box
Connection location for fire emergency and VESDAnet signals
3
415/240V 3-phase, wye,
4-wire
A feed power for IT Section A electrical busways and house power
4
415/240V 3-phase, wye,
4-wire
B feed power for IT Section A electrical busways and house power
5
Mechanical power feed
cabinet
A and B feed power for the IT Section A AHU
6
Mechanical power feed
cabinet
A and B feed power for the IT Section B AHU
7
415/240V 3-phase, wye,
4-wire
B feed power for IT Section B electrical busways and house power
8
415/240V 3-phase, wye,
4-wire
A feed power for IT Section B electrical busways and house power
Main breaker locations