HP Performance Optimized Data Center (POD) 240a User Manual

Page of 93
 
Power, electrical, and controls  32 
Drop boxes 
The internal electrical busways provide a location to connect each of the drop boxes, which then power the 
PDUs. For each IT section, stagger the drop boxes on the electrical busways by connecting one drop box to 
busway #1 and connecting the next drop box to busway #2. A staggered configuration allows for load 
balancing with the rack equipment and is necessary to create redundancy. 
Side view shown 
 
Disabling power 
 
To disable power to a single PDU, open the drop box breaker feeding that PDU and disconnect the PDU 
from the drop box. 
 
To disable power to a single rack, open the corresponding breakers on the drop boxes feeding each of 
the PDUs installed in that rack. 
 
To disable power to a single electrical busway, open the appropriate breaker for that busway on the 
corresponding electrical busway panel outside of the HP POD 240e NA. 
 
To disable power to all racks on the A-side busways, open each breaker for each busway on the 
corresponding electrical panel outside of the HP POD 240e NA. 
 
Rack power 
Power is provided to each rack by PDUs and drop boxes. The PDUs are powered by the drop boxes attached 
to each electrical busway. For more information about electrical busway drop boxes, see the HP 
Performance Optimized Datacenter 240e NA Maintenance and Service Guide
 
Feature 
Specification 
Rack type 
HP POD 240e NA rack 
Max number of racks 
44 (22 per IT section) 
Max U space per rack 
50U 
Max U space per HP POD 240e NA  2,200U 
Total number of PDU's 
88 (2 per rack)