HP Performance Optimized Data Center (POD) 240a User Manual
Environmental control system 49
Information displayed Description
Static pressure
Indicates the cold and hot aisle static pressure
readings for each Adiabatic in relation to the
external ambient pressure
Temps
Indicates the cold and hot aisle temperature
readings for each Adiabatic unit
readings for each Adiabatic unit
Fan speed
Indicates the fan speed for each Adiabatic unit
Water valve
Indicates the water valve percentage for each
Adiabatic unit
Dampers
Indicates the damper position for each Adiabatic
unit
To change the charts that display at the bottom of the screen:
1.
Click a chart to bring up the chart menu.
2.
Select the information that you want to view.
Alarms chart
The alarms chart displays critical and warning alarms that are active in the system. For more information, see
)."
Electrical Cabinets screen
The Electrical Cabinets screen displays detailed power meter information that is monitored from the HP POD
240e NA power input. This screen displays the voltage and current average for all 3-phase electrical feeds.
The apparent and real power values are the sum of all 3-phase electrical feeds. The values shown on this
The apparent and real power values are the sum of all 3-phase electrical feeds. The values shown on this
screen are included in the PUE calculations for the HP POD 240e NA.
The power information that displays on this screen is read-only and cannot be altered.
Static IP addresses can be viewed from this screen when the customer-level password is entered.
The power information that displays on this screen is read-only and cannot be altered.
Static IP addresses can be viewed from this screen when the customer-level password is entered.
IMPORTANT:
The ECS system subtracts the power measurements for the house panel from the
Starline power measurements to be sure that the PUE measurements are accurate.