Environmental control system  54 
Configure 
You can see the Configure menu when you enter the customer-level password. This menu allows you to 
configure alarm setpoints and Adiabatic control settings in the ECS system. 
The following menus are available when you select the Configure menu: 
 
Control settings (on page 
) 
 
HMI settings (on page 
) 
 
 
CAUTION: 
 Making any change to the ECS in the customer-level area can cause the AHU to fail. 
Only authorized, qualified, and trained personnel should change configuration settings in the 
customer-level area of the ECS. Any changes to the configuration settings in the customer-level 
area might void your warranty. 
 
 
Control settings 
 
 
IMPORTANT:
  You can only access this menu after you enter a customer-level password. 
  
 
IMPORTANT:
  The ECS parameters must only be set by qualified service personnel. 
  
The Control Settings menu displays the Adiabatic Control Settings for IT section A and IT section B. The 
following settings can be configured from the Adiabatic Control Settings screen: