Life safety systems  21 
Fire suppression sequence of operations 
After the fire suppression system is activated by a VESDA signal or a manual fire pull, a 30-second 
countdown begins before the fire suppression agent is released to the HP POD 40c G2 interior through the 
fire system piping. 
VESDA initiation 
Press the fire suppression abort button to interrupt the fire suppression release countdown for 30 seconds. The 
abort button can be pressed multiple times to interrupt fire suppression release agent countdown for an 
additional 30 seconds until the 30-second fire suppression release countdown has been exhausted. 
Press and hold the abort button to stop the immediate activation of the fire suppression system until the button 
is released. When the button is released, the 30-second delay will begin. The remaining fire suppression 
release agent countdown will continue after the 30-second delay until the time is exhausted. 
Manual initiation 
The fire suppression abort button will not delay the release of the fire suppression agent if a manual fire pull 
was activated. All personnel should immediately evacuate. 
 
Emergency egress 
The HP POD 40c G2 includes the following features for life safety egress on all access doors: 
 
Panic bar 
 
Door strikes 
Standard hardware—Door strikes 
Optional hardware—Electric door strikes 
Each personnel door includes a standard panic bar to ensure safe exit. The optional egress hardware 
included in the HP POD 40c G2 (including electric panic bars, electric strikes, and magnetic locks) are tied 
to the fire alarm to enable uninhibited egress in the event of an emergency.