Environmental control system  34 
By connecting your HP POD 40c G2 to a BMS system, you can monitor the various parameters and alarms. 
For more information, see "Navigating the ECS interface (on page 
)." The complete list of parameters and 
alarms that can be monitored will be discussed with your facilities personnel. 
  
 
IMPORTANT:
  If your site does not have a BMS, HP POD 40c G2 ECS data can be sent to and 
viewed from a set IP address. Communication occurs through an Ethernet cable that is connected 
to the demarcation box (on page 
). 
  
 
Satellite control boxes 
The satellite control boxes facilitate communication from the ECS to the cooling system fans. Each satellite 
control box controls the fans in the zone that corresponds with its location. 
The HP POD 40c G2 has six satellite control boxes, one box per cooling zone. 
Top view shown 
 
 
Sensors 
The HP POD 40c G2 has several temperature and pressure sensors that monitor the environmental factors 
and communicate data back to the ECS. 
 
The values from the temperature sensors are calculated together to determine an average temperature 
for each aisle of the HP POD 40c G2. 
 
The pressure sensors measure the differential pressure between the hot aisle and the cold aisle. 
Cold aisle sensors