HP Performance Optimized Data Center (POD) 40c User Manual

Page of 84
 
Environmental control system  43 
Overview screen 
The Overview screen appears upon activation of and displays an overview of the ECS components and the 
status of each component. 
 
The Overview screen displays the following information. 
 
Information 
Description 
EPO system status 
Indicates the status of the EPO system: 
 
Green—The EPO system is armed and 
operational. 
 
Red—The EPO system is activated. 
Average voltage, current, 
and power drawn on the A 
and B busways 
Indicates electrical usage 
Relative humidity 
Indicates the relative humidity percentages from 
each of the humidity sensors 
Differential pressure values  Indicates the differential pressure values from 
each of the differential pressure zones between 
the hot aisle and the cold aisle 
Door access indicators 
Indicates whether an access door is open or 
closed 
Fan speed 
Indicates the fan bank speed percentage 
Hot aisle temperature 
Indicates the average temperature in the hot aisle