HP Performance Optimized Data Center (POD) 40c User Manual

Page of 84
 
Cooling system  59 
Side view shown 
 
 
Item 
Component 
Description 
Heat exchanger 
Use chilled facility water to cool the air in the HP POD 40c G2 
Drain pan sensor 
Detects excessive amounts of condensate in the drain pan and sends an alarm 
signal to the ECS 
Drain pan 
Collects and directs heat exchanger condensate to the condensate drain 
Condensation drain 
Removes condensation from the drain tray to the exterior of the HP POD 40c 
G2  
Header drain pan 
Provides leak detection for the chilled water supply and the chilled water 
supply return 
 
 
Fans 
HP POD 40c G2 fans operate at variable speeds to maintain the following setpoints programmed in the ECS. 
The setpoints are maintained in the following order: 
1. 
Differential pressure setpoint between the hot and cold aisles 
2. 
Hot aisle temperature setpoint 
The fan speed adjusts to maintain both setpoints. Do not manually adjust the fan speed. 
  
 
IMPORTANT:
  HP recommends leaving the fans in AUTO mode during normal operation.