Galaxy 3 Series Installation Manual
5-4
Configuring as a Stand-Alone MAX
3
1. Ensure that the MAX
3
 is connected to the Galaxy (RS485 AB line) and the MAX mode is enabled
(option 63.2.1 = OPTIONS.MAX.MAX Mode).
2. Select option 63.2.2 = OPTIONS.MAX.MAX Address and press the ent key; the Galaxy
searches for the MAX
3
 with the highest address (the new MAX
3
 reader).   The Galaxy panel may prompt
(depending on model) for the AB line (1 – 4) that is to be searched; select the line and press the ent key.
On locating the MAX address, the keypad prompts for the 
OPERATING MODE
 of MAX to be assigned:
select 1 = Standalone and press the ent key. The MAX
3
 reader is readdressed as 32.
When the reprogramming is complete the MAX
3
 bleeps, LED 3-7 on the MAX
3
 switches on and the keypad
display returns to 2 = MAX Address.
3. Disconnect the AB line from the MAX
3
 reader. Ensure that all other modules (keypads, RIOs and on-line
MAX
3
 readers) are still daisy-chained into the Galaxy panel.  If the MAX
3
 reader is the last module on the
AB line, remove the 680
Ω end of line resistor and put it into the last module on the line.
4. The MAX
3
 reader is now programmed as a stand-alone module in sleep mode (LEDs  3–7  on) and can
be programmed using the MAX
3
 cards (refer to Programming Stand-Alone MAX
3
 Readers).