Hach sc1000 User Manual

Page of 150
73
Standard Operations
5.15 Formula editor for output and relay card
Formulas can be used as additional signal source for output and relay cards (DIN rail and 
expansion cards). Each channel of the output or relay card can be used to run a formula. 
The result of a formula can be used the same way like real measured values.
By using formulas, “virtual measurements” can be created (for example average values 
from measured values of multiple probes). The virtual measured value is calculated from 
the measured readings of other probes.
5.15.1 Add a formula
To add a formula: 
1. Select SYSTEM SETUP, 
a. for an output card continue with OUTPUT SETUP, mA OUTPUT INT/EXT, 
OUTPUT 1-4, SELECT SOURCE, SET FORMULA. 
b. for a relay card continue with RELAY, RELAY INT/EXT, RELAY 1-4, SENSOR,
SET FORMULA.
2. The main menu of the formula editor is displayed (
). Tap on the text fields to 
edit the Name, Location, Unit, Parameter and Formula. 
Figure 49  Main menu of the formula editor
Table 21   Formula settings
Function
Description
Name
Enter a reference name for identification in display views and log files (Maximum of 16 
characters).
Location
Enter an additional location information for unique identification (Maximum of 16 characters)
Unit
Enter a virtual measurement unit (Maximum of 6 characters).
Parameter
Enter a virtual measurement parameter (Maximum of 6 characters).
Formula
Enter a formula, which calculates the virtual measurement value. The formula can use 
letters A, B, C as shortcuts for other measurement values (
).
Definition for letters A, B, C
Lists the existing assignments (for other measurement values).
Add (Tag)
Creates a new letter (A, B, C) as a place holder for another new measurement value.