Guardian Technologies QT10068 User Manual

Page of 4
APPLICATION
& ENGINEERING DATA
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage.  No overload capability is available for this rating.  (All ratings in accordance with BS5514, 
ISO3046 and DIN6271).  (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).
COMMERCIAL 100 kW
GENERATOR SPECIFICATIONS
TYPE ................................................................................................................Synchronous
ROTOR INSULATION ................................................................................................ Class H
STATOR INSULATION .............................................................................................. Class H
TOTAL HARMONIC DISTORTION ...............................................................................<3.5%
TELEPHONE INTERFERENCE FACTOR (TIF) .................................................................. <50
ALTERNATOR OUTPUT LEADS 3 PHASE ....................................................................4 wire
BEARINGS...........................................................................................................Sealed Ball
COUPLING ...........................................................................................................Gear  Drive
LOAD CAPACITY (STANDBY RATING) ..................................................................... 100 kW
EXCITATION SYSTEM ...........................................................................................Brushless
NOTE:   Generator rating and performance in accordance with 
ISO8528-5, BS5514, SAE J1349, ISO3046, and DIN6271 standards.
GENERATOR FEATURES
 Revolving field heavy duty generator
 Quiet drive coupling
 Operating temperature rise 120 °C above a 40 °C ambient
 Insulation is Class H rated at 150 °C rise
 All prototype models have passed three phase short circuit testing
VOLTAGE REGULATOR
TYPE ................................................................................................................... Full  Digital
SENSING..................................................................................................................3 Phase
REGULATION ............................................................................................................± 1/4%
FEATURES............................................................................ Built into H-100 Control Panel
 V/F 
Adjustable
 
Adjustable Voltage and Gain
CONTROL PANEL FEATURES
 
TWO FOUR LINE LCD DISPLAYS READ:
 
  • Voltage (all phases) 
• Current (all phases)
 
  • Power factor 
• kW
 
  • kVAR 
• Transfer switch status
 
  • Engine speed 
• Low fuel pressure
 
  • Run hours 
• Service reminders
 
  • Fault history 
• Oil pressure
 
  • Coolant temperature 
• Time and date
 
  • Low oil pressure shutdown 
• High coolant temperature shutdown
  
• 
Overvoltage 
• 
Overspeed
 
  • Low coolant level 
• ATS selection
 
  • Not in auto position (flashing light) 
• Exercise speed
 
 
 
INTERNAL FUNCTIONS:
  
• 
I2T function for alternator protection from line to neutral and line to line short circuits
 
  • Emergency stop
 
  • Programmable auto crank function
 
  • 2 wire start for any transfer switch
 
  • Communicates with the Generac HTS transfer switch
 
  • Built-in 7 day exerciser
 
  • Adjustable engine speed at exerciser
 
  • RS232 port for GenLink
®
 control
 
  • RS485 port remote communication
 
  • Canbus addressable
 
  • Governor controller and voltage regulator are built into the master control board
 
  • Temperature range -40 °
C to 70 °C
ENGINE SPECIFICATIONS
MAKE ......................................................................................................................  Generac
MODEL ......................................................................................................................V Type
CYLINDERS ..................................................................................................................... 10
DISPLACEMENT ..................................................................................................... 6.8  Liter
BORE............................................................................................................................. 3.55
STROKE ........................................................................................................................ 4.17
COMPRESSION RATIO ................................................................................................... 9:1
INTAKE AIR SYSTEM ..............................................................................Naturally Aspirated
VALVE SEATS ........................................................................................................ Hardened
LIFTER TYPE ......................................................................................................... Hydraulic
GOVERNOR SPECIFICATIONS
TYPE .....................................................................................................................Electronic
FREQUENCY REGULATION ...............................................................................Isochronous
STEADY STATE REGULATION .................................................................................± 0.25%
All functions are factory preset.
Individual parameter adjustments can be made via GenLink
®
.
ENGINE LUBRICATION SYSTEM
OIL PUMP ..................................................................................................................... Gear
OIL FILTER ..................................................................................Full flow spin-on cartridge
CRANKCASE CAPACITY ......................................................................................... 5 Quarts
ENGINE COOLING SYSTEM
TYPE ......................................................................................................................... Closed
WATER PUMP ......................................................................................................Belt driven
FAN SPEED .................................................................................................................. 1670
FAN DIAMETER ..................................................................................................... 26 inches
FAN MODE .................................................................................................................. Puller
FUEL SYSTEM
FUEL TYPE ................................................................................Natural gas, propane vapor
CARBURETOR .....................................................................................................Down  Draft
SECONDARY FUEL REGULATOR ........................................................................... Standard
FUEL SHUT OFF SOLENOID .................................................................................. Standard
OPERATING FUEL PRESSURE .......................................................................11” - 14” H2O
ELECTRICAL SYSTEM
BATTERY CHARGE ALTERNATOR .....................................................................12V 30 Amp
STATIC BATTERY CHARGER ...............................................................................12V 2 Amp
RECOMMENDED BATTERY .................................................................Group 24F, 525 CCA
SYSTEM VOLTAGE.................................................................................................. 12 Volts