Gigabyte 7014 User Manual

Page of 152
 Rev.  051208 
 
        
page 136 of 152
 
N-Ring get interval 
Command Name 
n-ring get interval 
Description 
To display the Self-Health Packet interval and missed threshold. 
Syntax 
n-ring get interval  
Parameters 
None 
Example 
N-TRON/Admin#[1]> n-ring get interval 
 
Self Health Packet interval is 1 
Maximum Missed Packets is 2 
NOTES 
Default:  interval=1, missed=2 
 
 
 
N-Ring set interval 
Command Name 
n-ring set interval 
Description  
Sets the Self-Health Packet interval and missed threshold. 
Syntax 
n-ring set interval <interval> [missed] 
Parameters  
interval and missed 
Examples 
N-TRON/Admin#[36]n-ring/set> n-ring set interval 1 3 
 
Self Health Packet interval set to 1 
Maximum Missed Packets set to 3 
NOTES 
The  interval  is  in  10  millisecond  increments.    The  missed  threshold  sets 
how many missed Self-Health Packets constitute a fault. 
 
N-Ring get mode 
Command Name 
n-ring get mode 
Description 
To display the current N-Ring Mode. 
Syntax 
n-ring get mode   
Parameters 
None 
Example 
N-TRON/Admin#[1]> n-ring get mode 
 
N-Ring Mode : AutoMember 
Port Set  : 100 
VLAN ID :   1 
Tagging :   Untagged 
NOTES 
Do not use Trunking on a switch that is directly in an active N-Ring. 
 
N-Ring set
 
mode 
Command Name 
n-ring set mode 
Description  
Sets the current N-Ring Mode. Sets ring ports, vlanid and tagging,  if manager mode. 
Syntax 
n-ring set mode <manager|automember|disable> [-rp <100|GB>] [-vlanid <id>] [-
tagging <tagged|untagged>]
 
Parameters  
manager|automember|disable 
       N-Ring mode 
A|E 
       N-Ring ports, 100 for ports FX1 and FX2, while GB for ports GB1 and GB2 
id 
       Unique vlan id (1 - 4094). Default is 3333. 
tagged|untagged 
       Determines whether the N-Ring ports are members of the VLANs 
       Tagged or Untagged ports.  Default is Tagged. 
Examples 
N-Ring Mode set to automember 
................ 
................ 

Device is Going for Reboot.... 
 
N-TRON/Admin#[3]> n-ring set mode manager -rp GB 
 
N-Ring Mode set to manager 
Port Set to be used is GB