GE Flame Tracker Data Sheet

Page of 2
920-613B 
©2014 General Electric Company. All Rights Reserved. Specifications are subject to change without notice. GE is a registered trademark of General Electric Company. Other company or product names mentioned in this 
document may be trademarks or registered trademarks of their respective companies, which are not affiliated with GE.
www.ge-mcs.com
GE 
Measurement & Control
8499 Darrow Road
Twinsburg, OH 44087
1 (330) 425-3755
rsweb@ge.com 
www.ge-mcs.com
*Trademark of General Electric Company
Sensor Responsivity and
Hydrocarbon Flame Emission Spectrum
Power Requirements 24 VDC nominal, 12-30 VDC @ 100 mA
Output
4-20 mA (a module to convert output to 
other controller inputs is available)
Response Time
< 25 milliseconds
Temperature Range Hot End -40ºF to +392ºF  
(-40ºC to +200ºC) 
Cool End -40ºF to +302ºF  
(-40ºC to +150ºC)
Process Pressure
To 400 psig (2.8 MPa)
Sensitivity
5 mA @ 1x10
10
 photons/in
2
/sec.  
@ 310 nm
Body Mount
AISI 316 Stainless Steel
Housing
AISI 304 Stainless Steel 
(sealed and Argon filled)
Mechanical Interface 3/4” NPT female
Sensing Element
Silicon Carbide (SiC) photodiode
Operating
Material
Specifications
SystemConfiguration
100
80
60
40
20
0
200
250
300
350
400
450
Wavelength, nm
Relative Response (%
)
Flame Emission
GE SiC Flame Detector
Optical&electricalcharacteristicscloselymatchUVflameemissions
GM (Geiger-Muller) Tube
Peaksensitivityisat190nm,whileflameintensitypeakis310nm