3. n : 1 Connection (Multi-link 2)
3-11
Ser
3.
n : 1 Connection 
(Multi-link 2)
Multi-link 2
• One PLC is connected to a maximum of four V7 series.
• An original network is created where the V7 series (Local Port 1) that is directly 
connected to the PLC is the master station, and other three V7 series are slave 
stations.  Only the master station makes communications directly with the PLC, and the 
slave stations make communications with the PLC via the master station.
• Communications between the V7 master station and the PLC depend on the 
communication speed set on the PLC.  The maximum available speed for the V7 series 
is 115 kbps, which is higher than the one available with multi-link connection described 
in “4. n : 1 Connection (Multi-link).”
• This multi-link connection is available with almost all the PLC models that support 1 : 1 
connection (refer to the Appendix).  The connection between the master station and the 
PLC is the same as the one for 1 : 1 connection).
• Use the RS-485 2-wire connection between stations of the V7 series.  Please use 
Hakko Electronics’ multi-link 2 master cable (V6-MLT) for connection between the 
master station (Local Port 1) and the slave station (Local Port 2).
• In the following cases, multi-link 2 connection is not available.
1. A communication interface unit (example: OPCN-1, CC-LINK, Ethernet, etc) is 
used.
2. The V7 series (master or slave station) is used for the temperature control network 
or PLC2Way function.
PLC
RS-232C
RS-422
RS-485
CN1
MJ2
CN1
CN1
CN1
F1
F2
F3
F4
F5
F6
F7
SYSTEM
POWER
F1
F2
F3
F4
F5
F6
F7
SYSTEM
POWER
F1
F2
F3
F4
F5
F6
F7
SYSTEM
POWER
F1
F2
F3
F4
F5
F6
F7
SYSTEM
POWER
Hakko Electronics’ cable
“V6-MLT” (3 m)
RS-485 connection
V7 master station
V7 slave station
V7 slave station
Local Port 1
Local Port 2
Local Port 3
Local Port 4
V7 slave station