Epson V7 User Manual

Page of 344
3-24 
6. V-Link
V-SFT Setting
The V-SFT settings required for V-Link are explained.
V-Link Setting
1. Click [System Setting] 
→ [V-Link Setting].
2. The [V-Link Setting] dialog is displayed.
3. Check [
 Use MJ port as V-Link] and make the setting for communications between 
the V7 series and the computer.
[Refer to Modular]
Select the modular jack to be used.  Modular Jack 1/Modular Jack 2
[Baud Rate]
4800 / 9600 / 19200 / 38400 / 57600 / 115 kbps
[Local Port] (1 to 31)
Set the port number of the V7 series.
[Send Delay Time] (msec)
Set a time delay in sending a response after receipt of data.
[Parity]
None/Odd/Even
[Signal Level]
RS-232C / RS-485
With RS-232C, one V7 series can be connected; with RS-485, a maximum of 31 V7 
series can be connected.
[Data Length]
7-bit/8-bit
[Stop Bit]
1-bit/2-bit
[Use sum check]
Check this option when using a sum check.
[Add CR/LF]
Check this option when adding CR/LF.