Epson V7 User Manual

Page of 344
4-6 
1. Ethernet
AUI Connection
• 10BASE5
The following devices are required for 10BASE5 connection:
- Coaxial cable for 10BASE5
- AUI  cable
- N-type connector
- N-type terminator
- Transceiver
- Power supply for the transceiver: 12 VDC
• Transceiver
Use the transceiver equipped with the SQE TEST function.  (SQE TEST: Signal Quality 
Error Test)
Recommended transceiver
* The I/F unit may be broken if the AUI connector is subject to strong force.  Use the AUI 
cable when connecting the transceiver.
* When the power lamp of the transceiver is not turned on, check the wiring of 12 VDC 
power supply, then replace the fuse (refer to page 4-4) of the I/F unit CU-03.  For the 
replacement procedure, refer to the manual “CU-03 OPERATING INSTRUCTIONS,” 
attached to CU-03.
• 10BASE2
The following devices are required for 10BASE2 connection:
- Coaxial cable for 10BASE2
- AUI  cable
- T-type adaptor
- Terminator for 10BASE2
- Transceiver
- Power supply for the transceiver: 12VDC
Manufacturer
Type
Allied Telesis
CentreCOM 107
CU-03
V7
PLC
Maximum segments:
5
Maximum network distance: 2500 m
Maximum network nodes:
100 sets
Ethernet
unit
1 segment (max. 500 m, max. 100 nodes)
AUI cable
(max 50 m)
Transceiver
*1
N-type
terminator
N-type connector
Node
Node
Node
Repeater
Minimum node interval
2.5 m
To extend the length or 
increase the number of 
nodes, use repeaters.
*1: 12 V power supply is required for each transceiver.