4. HITACHI PLC
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
COMM-2H
If the transmission mode is any type other than listed the above, set the mode as shown 
below.
*1 Multi-link connection is not available.
CPU module
The peripheral port setting should be “transmission control protocol 1 without port.”  No 
other setting is available.
HIDIC-S10
α
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
0 for both ST No 
×10, ×1
0
Parity
Even
Even
Transmission mode
RS-232C
MODE7
Protocol 2 with port
RS-422
MODE9
Protocol 2 with port
Transmission code
Data length
7 (ASCII)
7
Stop bit
1
1
Sumcheck
Provided (fixed)
Item
Setting on PLC
V7 Comm. Parameter Setting
Transmission mode
RS-232C
MODE1
MODE2
MODE9
Protocol 1 without port
Protocol 1 with port
Protocol 2 without port
RS-422
MODE2
    Protocol 1 with port
*1
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
7
19200 bps