Epson V7 User Manual

Page of 344
5
7. YASKAWA PLC
5-51
Co
nne
CP9200SH/MP900
Available Memory
The available memory setting range varies depending on the PLC model.  Be sure to set within the 
range available with the PLC to be used.  Use [TYPE] when assigning the indirect memory for macro 
programs.
Memobus
CP9200SH/MP900
When setting the MB/IB memory, set the bit numbers in the hexadecimal notation.
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
1
1
Parity
Even
 Even
Transmission code
Data length
8
8
Stop bit
1
1
Error check
CRC (fixed)
Port delay timer
0 (fixed)
Memory
TYPE
Remarks
4
(word device)
0
3
(input register)
1
Including constant register, read only
R
(link register)
2
A
(extension register)
3
0
(coil)
4
D
(link coil)
5
1
(input relay)
6
Read only
7
(constant register)
7
Memory
TYPE
Remarks
MW
(holding register)
0
IW
(input register)
1
Read only
MB
(coil)
4
IB
(input relay)
6
Read only
MBxxxxx
DEC
Bit No.: HEX