Epson V7 User Manual

Page of 344
5
9. FUJI PLC
5-59
Co
nne
FLEX-PC CPU Port
Connect to the CPU port.  Communication parameters for the V7 series are automatically 
set.
FLEX-PC COM (T) (NJ Computer Link) Toyota Version
MICREX-F Series, FLEX-PC Series: Switch Setting
MODE switch:
RS-232C: 1
RS-485: 3
RS-485 Port Setting SW: 
“0” for both 
×10, ×1
RS-485 terminating resistance: ON
Character switches
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
0
0
Parity
 Even
Even
Transmission code
Data length
7
7
Stop bit
2
2
No
Setting
Contents
8
ON
Switch Setting
7
ON
With  parity
6
ON
Even
5
ON
7  bits
4
ON
1  bit
3
ON
Same as that set on V7 (normally 19200 bps)
2
ON
1
OFF