Epson V7 User Manual

Page of 344
5
11. Allen-Bradley PLC
5-73
Co
nne
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
PLC-5 series
SLC500 series
Micro Logix 1000
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
0
0
Parity
Even
Even
Transmission mode
RS-232C
RS-422
1785-KE not supported
Transmission code
Data length
8
8
Stop bit
1
1
Protocol
Full duplex (fixed)
Error check
BCC (fixed)
Response
NO (fixed)
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
0
0
Parity
Even
Even
Transmission mode
RS-232C
RS-422
Channel 0 not supported
Transmission code
Data length
8
8
Stop bit
1
1
Protocol
Full duplex (fixed)
Error check
BCC (fixed)
Response
NO (fixed)
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
9600 bps
9600 bps
Port
0
0
Parity
None (fixed)
 Not provided
Transmission code
Data length
8 (fixed)
8
Stop bit
1 (fixed)
1
Error check
CRC (fixed)