Epson V7 User Manual

Page of 344
5
19. LG PLC
5-109
Co
nne
MASTER-KxxxS
MASTER-KxxxS CNET / GLOFA CNET
Available Memory
The available memory setting range varies depending on the PLC model.  Be sure to set within the 
range available with the PLC to be used.  Use [TYPE] when assigning the indirect memory for macro 
programs.
MASTER-K10/60/200
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
38400 bps
38400 bps
Parity
None (fixed)
Transmission code
Data length
8 (fixed)
Stop bit
1 (fixed)
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
38400 bps
38400 bps
Parity
Not provided
Not provided
Transmission code
Data length
8
8
Stop bit
1
1
Memory
TYPE
Remarks
D
(data register)
0
M
(auxiliary relay)
1
P
(input/output relay)
2
Input: Read only
K
(keep relay)
3
TC
(timer/current value)
4
CC
(counter/current value)
5
TS
(timer/set value)
6
CS
(counter/set value)
7