Emerson 300510EN User Manual

Page of 246
System Configuration Manual 
300510EN, Rev AA
December 2010
5-53
Rosemount Raptor
Section 5. Installing a Raptor Level Gauging System
3. Select the Communication tab.
4. Verify the communication settings. The Connected to HUB field indicates 
which tank that the 5900S is associated with in the 2410 Tank Database. 
Normally, the single tank version of the Rosemount 2410 Tank Hub is 
used for Rosemount 5900S level gauges. In this case the Position in 
2410 HUB
 field will be equal to 1 since there is only one tank position 
that is used in the 2410 Tank Database. 
In case the multiple tank version of the Rosemount 2410 is used to 
connect several tanks, the level gauge can be mapped to another tank 
through the 2410 Tank Hub Properties/Tank Database window (in the 
WinSetup workspace, click the right mouse button on the 2410 icon and 
choose the Properties option). 
See “Tank Database Setup” on page 5-42 for more information on 
2410 Tank Database setup.
5. Verify that the Modbus address is correct. 
To change the Modbus address click the Change button to open the 
Change Address window:
This field shows which 2410 Tank 
Hub that the radar level gauge is 
connected to
This field shows the tank position 
in the 2410 Tank Database