Emerson Liebert PSA Line-Interactive UPS 500-1500VA User Manual
List of Events
109
Liebert
®
MultiLink
®
D.2 E
VENTS
FOR
UPS
The table below shows UPS-related events that might appear in the Viewer’s Event Configuration
tab, depending on the communication method used and the UPS model selected in the Viewer (see
• Contact Closure supports only the first three events in the table below.
• USB communication supports a subset of events in the table below, depending on the UPS model.
• The Advice portion is displayed when you click on the Advice button on a Liebert MultiLink pop-
• USB communication supports a subset of events in the table below, depending on the UPS model.
• The Advice portion is displayed when you click on the Advice button on a Liebert MultiLink pop-
up notification.
• Liebert MultiLink has three Severity levels: Informational, Impaired and Critical.
Table 14
Events from Event Configuration tab with UPS selected
Event
Description
Advice
Severity
Events supported by all device types
UPS Operating
On Battery
The UPS is discharging the
battery to supply power to the
load.
The UPS has detected a power outage or momentary
disturbance and is now providing battery power to
your computer. If you anticipate an extended power
problem, you should save your work and log out now.
Impaired
Low Battery
The UPS has reached a Low
Battery level. Time available to
remain on battery is very short.
Save your work and log out now as system shutdown
will begin shortly. The UPS is running out of battery
capacity and minimal battery backup runtime remains.
Critical
UPS Output
Returned From
Battery
The UPS has returned from an
abnormal utility input condition.
The UPS is receiving good utility power and is in the
normal mode of operation. You may continue working.
Informational
Weak Battery
Condition
(certain UPS
models only)
The UPS has reported that the
battery is in a weak condition
(with utility present). This is a
contact closure event only.
The UPS is reporting a weak battery condition which
indicates there currently is little capacity left in the
battery, or there is possibly a bad battery. If this
condition persists, the UPS battery may need to be
replaced.
If you need further assistance, please call Emerson
Technical Support.
Impaired
Events not supported by contact closure
UPS
Communication
Established
The Liebert MultiLink software
has established
communications via the serial
port. This could be from the
starting of the service, or a
reestablishment of
communication after an
interruption.
The Liebert MultiLink software has established
communication with the UPS and is now monitoring
status. This could be from the starting of the service,
or a reestablishment of communication after an
interruption.
Informational
UPS
Communication
Loss
An unexpected loss of
communications with the UPS
via the serial port.
Please verify that Liebert MultiLink is correctly
configured and that the physical connection between
the computer (or server) and UPS is properly installed.
If you need further assistance, please call Emerson
Technical Support.
Critical
UPS Output
Operating On
Bypass
The load has transferred to
bypass and is unprotected.
The UPS is on bypass and will be unable to power
your load in the event of a power failure. When a UPS
experiences an internal failure, the load is switched to
bypass as a protective measure. The UPS may have
been manually switched to bypass by a user. If a non-
user initiated bypass condition occurred, you should
investigate the condition of the UPS.
Impaired
Battery Fully
Charged
The UPS has reported that the
battery is fully charged.
The UPS battery is fully charged. You now have the
maximum amount of battery runtime available for any
future power outages.
Informational
Battery
Capacity XX%
or less
User defined event. The
battery capacity is equal to or
fallen below the defined level.
This event is enabled only
when operating on battery.
The battery capacity has fallen below a user-defined
level. Depending on where this level is, you will want
to take appropriate action such as saving your work
and logging off. The Battery Capacity level notification
is user configurable and can be modified in the “Event
Configuration” tab in Liebert MultiLink.
Impaired