Emerson Liebert PSA Line-Interactive UPS 500-1500VA User Manual

Page of 120
Configuring Liebert MultiLink for Your System
60
Liebert
®
 MutiLink
®
8.5.2 Event Actions - Notify
The Notify feature automatically generates messages (pop-up or console) about UPS-related events 
that appear on specified computer users’ screens.
• Check  (
) the Enable Notify Action box. This is required for the action to operate.
• The Initial Delay displays the time lapse between an event’s occurrence and when the 
notification message is sent. The Repeat Count box shows how many times Liebert MultiLink 
will send a message at intervals specified in the Repeat Interval box. 
For example, to start sending a notification 15 seconds after the Event occurs and then every 30 
seconds for a total of 5 times:
• Initial Delay = 15 sec
• Repeat Count = 5
• Repeat Interval = 30 sec
• Default messages have been set up for all events. These messages state the type of event, the time 
it occurred, the device involved and a description of the event. To view a message as it will appear 
on users’ screens, click on the Preview button. 
• To alter a message, click on the Edit button and enter the desired text in the Message window, as 
shown below. 
Enable 
box
Notify 
Action
Notification 
options 
depend on 
operating 
system