Emerson Liebert MC Microchannel Outdoor Condenser 28 - 220kW User Manual

Page of 68
Electrical Connections
23
Liebert
®
 MC
Key Electrical Details—Typical Connections, Premium Efficiency Control
1. Three-Phase Electrical Service—Terminals are on the top of the disconnect switch for one-fan 
and two-fan units. Terminals are on the bottom of the disconnect switch for three-fan and four-fan 
units. Three-phase service not by Emerson. See 4.1.1 - Wye vs. Delta Connection Power 
2. Earth Ground—Field lug terminal for earth ground connection. Ground terminal strip for fan 
motor ground connection.
3. Primary High-Voltage Entrance—Three 7/8" (22.2mm) diameter knockouts located at the 
bottom of the enclosure.
4. SPD Field Connection Terminals—High-voltage surge protection device (SPD) terminals. 
SPD is an optional device.
5. CANbus Terminal Connections—Field terminals for CANbus cable connection.
• 5A is the CANbus connectors.
• TB49-1 is the input terminal for CANbus high.
• TB49-3 is the input terminal for CANbus low.
• TB50-1 is the output terminal for CANbus high.
• TB50-3 is the output terminal for CANbus low.
• Each CANbus cable shield is connected to terminal “SH;” see 9 below.
• 5B is the “END OF LINE” jumper.
• 5C is the CANbus “DEVICE ADDRESS DIP SWITCH.” CANbus cable not by Liebert. See 
6. Remote Unit Shutdown—Replace exiting jumper between Terminals TB38-1 and TB38-2 with 
field-supplied normally closed switch having a minimum 75VA 24VAC rating. Use field-supplied 
Class 1 wiring.
7. Alarm Terminal Connections
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common, TB74-2 is 
normally open, and TB74-3 is normally closed. 1 Amp 24VAC is the maximum load. Use 
field-supplied Class 1 wiring.
b. Shutdown Alarm Relay indicates when condenser loses power, or when a critical alarm has 
occurred that shuts down the condenser unit. TB74-4 is common; TB74-5 is normally open;, 
and TB74-6 is normally closed. 1 Amp 24VAC is the maximum load. Use field-supplied 
Class 1 wiring.
8. Indoor Unit Interlock and SPD Alarm Terminals
a. On any call for compressor operation, normally open contact is closed across Terminals 70 and 
71 for Circuit 1, and normally open contact is closed across Terminals 70 and 230 for Circuit 2 
from indoor room unit.
b. During SPD alarm, normally open contact is closed across Terminals 12 and 13. SPD is an 
optional device.
9. CANbus Shield Terminal—Terminal for field shield connection of the CANbus field-supplied 
cables. The shield of CANbus field-supplied cables must not be connected to ground at the 
condenser.
10. Primary Low-Voltage Entrance—One 7/8” (22.2mm) diameter knockout that is free for 
customer low-voltage wiring.