Table 18
EC Fan alarm information
Alarm ID
Meaning
Possible Cause
Handling Method
(1-4) 00
EC Fan high link current
1. EC Fan is locked.
2. EC Fan is damaged.
For cause 1, check if EC Fan is 
locked.
For cause 2, replace EC Fan
(1-4) 01
EC Fan drive error
EC Fan is damaged.
Replace EC Fan
(1-4) 02
EC Fan earth to ground fault
EC Fan is damaged.
Replace EC Fan
(1-4) 03
EC Fan electronics heat sink thermal 
overload
1. EC Fan is locked.
2. EC Fan is damaged.
3. Ambient temperature is too 
high
For cause 1, check if EC Fan is 
locked.
For cause 2, replace EC Fan
For cause 3, check ambient 
temperature.
(1-4) 04
EC Fan Hall failure
EC Fan is damaged.
Replace EC Fan
(1-4) 05
EC Fan IGBT failure
EC Fan is damaged.
Replace EC Fan
(1-4) 06
EC Fan line fault
Power supply abnormal
Check power supply
(1-4) 07
EC Fan motor locked
Motor is locked
Check if EC Fan is locked.
(1-4) 08
EC Fan motor thermal overload
1. EC Fan is locked.
2. EC Fan is damaged.
3. Ambient temperature is too 
high
For cause 1, check if EC Fan is 
locked.
For cause 2, replace EC Fan
For cause 3, check ambient 
temperature.
(1-4) 09
EC Fan phase failure alarm
Phase failure
Check power supply
(1-4) 10
EC Fan-specific uncategorized alarm 
detected
Internal EC Fan issue
Re-boot condenser if fans not 
running. If alarm persists and fans 
not running, replace fan.
(1-4) 11
EC Fan-specific uncategorized 
warning detected
(1-4) 12
EC Fan electronics high-temperature 
condition.
1. EC Fan is locked.
2. EC Fan is damaged.
3. Ambient temperature is too 
high
For cause 1, check if EC Fan is 
locked.
For cause 2, replace EC Fan
For cause 3, check ambient 
temperature.
(1-4) 13
EC Fan high link voltage
1. EC Fan input power supply 
high voltage
2. EC Fan is damaged.
For cause 1, measure power 
supply voltage and check if the 
voltage is normal
For cause 2, replace EC Fan
(1-4) 14
EC Fan low link voltage
1. EC Fan input power supply low 
voltage
2. EC Fan detection error
(1-4) 15
EC Fan 485 communication failure
1. Communication between EC 
Fan and PCB board failure
2. EC Fan 485 communication 
failure
3. Board has problems
4. EC fan not receiving power
For cause 1, check EC Fan 
communication circuit
For cause 2, replace EC Fan
For cause 3, replace PCB board
For cause 4, check fan model is 
not set for “0”, check that the 
contactor for the particular fan is 
energized, and check fan fuses.
NOTE
(1-4) means the EC Fan addresses. For example, (1-4) 00 means 100 for EC Fan1, and means 