Emerson 5300 User Manual

Page of 42
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
1-10
ESTABLISH HART 
COMMUNICATION
The Rosemount 5300 Series and Rosemount 5400 Series can be configured 
using the Rosemount Radar Master (RRM) PC software or a Field 
Communicator. Configuration is done by sending HART commands through 
the HART to Modbus Converter (HMC) to the 5300/5400 transmitter 
electronics. To establish HART communication, connect to the MA/MB 
terminals, or to the HART terminals. Both alternatives are described below.
Connect to the MA/MB 
terminals
The 5300/5400 level transmitter can be configured with RRM using the MA, 
MB terminals.
An RS-485 Converter is required to connect to the transmitter.
The transmitter will try to establish communication using different protocols 
during 20 second timeslots from time of startup.
Figure 1-8. RS-485 Communication 
after startup
The transmitter will continue to use a communication protocol once 
communication has been established.
HART
20 seconds
Modbus RTU
20 seconds
Configured 
protocol 
(Modbus RTU, 
Levelmaster, 
or Modbus 
ASCII)
20 seconds
HART
20 seconds
Time
0 s
20 s
40 s
60 s
80 s
100 s
Configured 
protocol 
(Modbus RTU, 
Levelmaster, 
or Modbus 
ASCII)
20 seconds