Emerson 5300 User Manual

Page of 42
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
1-20
Modbus ASCII 
Communication Setup
The parameter, default, and configurable values are shown in Table 1-10 
below.
Table 1-10.  Modbus ASCII 
Communication Parameters
To reset the communication parameters to default Modbus ASCII settings, 
use the following Modbus Message:
HMC M1
Modbus ASCII Parameter Configuration Example
You want to use address 246 for the 5300/5400 transmitter and the host uses 
the following parameters:
Table 1-11.  Parameters Used by 
the Host (in case of Modbus ASCII, 
example)
To configure the 5300/5400 transmitter to communicate with the Host in this 
example, the following text string is written to the Modbus Message area.
HMC M1 A246 B9600 D7 PN S1.
NOTE
Include all the parameters when writing to the message area.
Note that an address must be unique on the bus.
HMC: These three letters are used for safety and will eliminate the risk of 
changing the configuration data by mistake.
M1: This means that the Modbus ASCII protocol is to be used.
A246A indicates that the following number is the new address (address 
246). Leading zeroes are not needed.
B9600B indicates that the following number is the new baud rate (1200, 
2400, 4800, 9600, 19200).
Parameter
Default value
Configurable values
Baud Rate
9600
1200, 2400, 4800, 9600, 19200
Start Bits
One
One
Data Bits
Seven
Seven, Eight
Parity
None
None, Odd, even
Stop Bits
One
One or Two
Address
1
1-255
Parameter
Value
Baud Rate
9600
Start Bits
One
Data Bits
Seven
Parity
None
Stop Bits
One