Emerson Liebert Economizer Solutions User Manual

Page of 32
Operation
18
Figure 10 Liebert DS setpoints screen, page 4 of 6
DT between Room / Outdoor Type—Sets the activation point of the ambient dry bulb outdoor 
temperature as it relates to either an indoor actual temperature or temperature setpoint. If set to 
“Temp,” the outdoor dry bulb temperature is compared to the return temperature actual value. If set 
to “Set,” the outdoor dry bulb temperature is compared to the return temperature setpoint. If set to 
“Disable,” the outdoor temperature will not be compared to the return sensor value for activation. 
When set to “Temp” or “Set,” the outdoor temperature must be lower than the room temperature 
setpoint or the actual return temperature sensor reading..
In most applications, this parameter will be set to “Temp” because the outdoor air temperature will 
reduce cooling costs as long as the outdoor air is below the return air temperature to the primary 
cooling unit. This remains true even when the outdoor temperature is higher than the supply control 
setpoint. The following examples assume that the unit is set for supply air control and that the 
moisture content of the outdoor air is within the allowable range.
Example 1
• Return Temperature: 90°F (32°C)
• Outdoor Temperature: 80°F (27°C)
• Supply Air Temperature: 60°F (16°C)
The conditions in this example would result in a reduction of 10°F entering the unit and would 
extend the operating range of the Liebert Air Economizer. The outdoor damper would be 100% 
open and the mechanical cooling would be utilized to achieve the 60°F (16°C) supply temperature 
setpoint.
Example 2
• Return Temperature: 75°F (24°C)
• Outdoor Temperature: 80°F (27°C)
• Supply Air Temperature Setpoint: 60°F (16°C)
In this example, the cooling unit would not use outdoor air because it is warmer than the actual 
return temperature to the CRAC.
Example 3
• Return Temperature: 75°F (24°C)
• Outdoor Temperature: 40°F (4°C)
• Supply Air Temperature: 60°F (16°C)
In this example, the cooling unit would open the outdoor damper based on the amount of cooling 
needed to satisfy the supply air temperature setpoint. The unit should be able to satisfy the sup-
ply air setpoint with Liebert Air Economizer operation only.
SETPOINTS (pg 4 of 6)
to change parameter
to confirm
to select parameter
for next/previous unit
then 
UNIT   01
PASSWORD   (Actual Level  0)
????
DT between Room / Outdoor Type
Disable
DT between Room Air / Outdoor
°F
DT between Room / FC Type
Disable
DT between Room Air FC Fluid
°F
Minimum CW Temp
Disable
Minimum CW Temp Value
°F
Lockout FC at FC Fluid below
48°F
Transition Change
100 .0%
S134
S135
S136
S137
S138
S139
S140
S141
S142
S143
S144